CYKYL-O-F

Place of use

For household appliances (refrigators, spin dryers, etc.) under medium mechanical stresses, also in damp and wet spaces. 

Structure

  • Fine-stranded copper conductor.
  • PVC insulation.
  • PVC outer jacket.

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C
28-62000001 2x1,5 6,7x4 46 100 13,3 / /
28-62000002 2x2,5 7,7x4,5 72 100 7,98 / /
28-62000003 2x4 9,4x5,5 118 100 4,95 / /
28-62000004 3x1,5 9,1x4 67 100 13,3 / /
28-62000005 3x2,5 11x4,5 121 100 7,98 / /
28-62000006 3x4 12,9x5,5 159 100 4,95 / /

Technical Info

Maximum conductor operating temperature: +70 o C

 Working temperature: -15o C to + 70o C

Lowest installation temperature: -5 o C

Maximum short-circuit conductor temperature: +160 o C

Minimum bending radius: 10 x D, D – overall diameter

Dielectric test voltage 50Hz: 2,5kV